HIPOWER HNI Spark-Ignited Standby Generators
HIPOWER HNI Spark-Ignited Standby Generator Series
HIPOWER HNI spark-ignited standby generators are designed for stationary commercial, industrial, and mission-critical applications. The HNI series ranges from 30 kW to 1,000 kW and offers natural gas, LP/LPV, and dual-fuel configurations depending on model, along with a wide range of enclosure, control, breaker, and engineered options.
HIPOWER HNI Standby Generator Range
HIPOWER HNI spark-ignited standby generators are available from 30 kW to 1,000 kW for commercial, industrial, and mission-critical standby power applications.
|
Series |
Standby Range |
Fuel Options |
Best Fit |
|---|---|---|---|
|
HNI 30-80 |
30-80 kW |
Natural Gas / LP (model dependent) |
Small commercial, agriculture, light industrial |
|
HNI 100-200 |
99.4-200 kW |
Natural Gas / LP (model dependent) |
Commercial facilities, healthcare, manufacturing |
|
HNI 250-500 |
250-500 kW |
Model-dependent spark-ignited configurations |
Larger commercial and industrial standby |
|
HNI 650-1000 |
650-1,000 kW |
Large spark-ignited standby configurations |
Manufacturing, data centers, large facilities |
HNI Features & Configurable Options
HIPOWER HNI generators combine standard heavy-duty components with configurable and engineered options for enclosures, controls, electrical systems, breakers, alternators, and application-specific requirements.
Enclosure Configurations
Open skid, Level 1, and Level 2 sound-attenuated enclosure options are available, including aluminum enclosure configurations. Additional options include gravity dampers and motorized air inlet dampers on applicable configurations.
Controls & I/O Expansion
The HNI series uses DSE 7410 controls, with available spare inputs and outputs, DSENet expansion modules, and remote display options on applicable models.
Circuit Breaker Options
Available breaker configurations include LSI, LS/I, LSIG, and thermo-magnetic trip options, along with secondary breakers, shunt trips, auxiliary contacts, and mechanical lugs.
Electrical Accessories
Available electrical options include battery warmers, battery chargers, remote E-stops, GFCI receptacles, relay outputs, control-panel heaters, remote annunciators, and enclosure lighting.
Stamford Alternator System
HNI generators use Stamford alternators with Class H insulation. Depending on model and configuration, options include PMG excitation, anti-condensation heaters, RTDs, tropical coating, and alternator upsizing.
Testing & Engineered Options
Extended testing, custom testing, extended warranty options, spring isolators, fluid-containment pans, third-breaker systems, and other engineered configurations are available depending on the application.
HNI Applications & Industries
HIPOWER HNI spark-ignited standby generators are designed for a wide range of commercial, industrial, agricultural, and mission-critical applications.
Oil & Gas
Standby power for oil and gas facilities and other demanding industrial applications.
Hospitality
Backup power for hotels, resorts, restaurants, and other hospitality facilities.
Agriculture
Reliable standby power for farms, livestock operations, and other agricultural facilities.
Data Management
Backup power for data management facilities and other operations where power continuity is critical.
Manufacturing
Standby generator solutions for plants, warehouses, production facilities, and industrial operations.
Healthcare
Backup power for hospitals, clinics, medical offices, and other healthcare facilities.
Certifications, Warranty & Reliability
Certifications & Compliance
HIPOWER identifies the HNI series with UL, NFPA 110, EPA, ANSI, and CSA certifications/compliance, depending on proper installation and selected options.
2-Year / 2,000-Hour Warranty
HIPOWER HNI generators include a standard limited parts-and-labor warranty of 2 years or 2,000 hours, whichever occurs first.
Heavy-Duty Standby Design
The HNI series is built for stationary standby applications using radiator-cooled industrial spark-ignited engines and Stamford alternators with Class H insulation.
HNI Technical Specifications
Review key performance, engine, alternator, and configuration data across the HIPOWER HNI spark-ignited standby generator lineup.
HNI 30-200 Technical Data
|
Spec |
HNI 30 |
HNI 40 |
HNI 50 |
HNI 60 |
HNI 80 |
HNI 100 |
HNI 125 |
HNI 150 |
HNI 200 |
|---|---|---|---|---|---|---|---|---|---|
|
Standby Power (kW) |
30 |
40 |
50 |
60 |
80 |
99.4 |
125 |
150 |
200 |
|
Standby Power (kVA) |
37.5 |
50 |
62.5 |
75 |
100 |
124.3 |
156 |
187.5 |
250 |
|
Amps @ 208V |
104 |
138 |
173.5 |
208 |
277 |
341 |
434 |
521 |
694 |
|
Amps @ 480V |
45 |
60 |
75.2 |
90 |
120 |
149.4 |
188 |
226 |
300 |
|
Amps @ 600V |
36 |
48 |
60.1 |
72 |
96 |
119.3 |
151 |
180 |
240 |
|
Sound @ 23' / 100% Load |
71 |
77 |
77 |
77 |
77 |
78 |
78 |
78 |
78 |
|
Ambient Capability °F/°C |
113/45 |
113/45 |
113/45 |
113/45 |
113/45 |
120/50 |
120/50 |
120/50 |
104/40 |
|
NG Fuel Consumption ft³/h |
578.3 |
1,039.2 |
1,039.2 |
1,039.2 |
1,039.2 |
1,247 |
1,940 |
1,940 |
2,431 |
|
Engine Manufacturer |
Origin |
Origin |
Origin |
Origin |
Origin |
PSI |
PSI |
PSI |
PSI |
|
Engine Model |
OE36LCTFC |
OE361LCTFTC |
OE361LCTFTC |
OE361LCTFTC |
OE361LCTFTC |
5.7LTCAC |
8.8LTCAC |
8.8LTCAC |
8.8LTCACHO |
|
EPA Certified |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Engine HP |
60 |
128.9 |
128.9 |
128.9 |
128.9 |
163.5 |
261.5 |
261.5 |
315.8 |
|
Stamford Alternator |
S1L2-J41 |
S1L2-N41 |
UCI224D |
UCI224E |
UCI274C |
UCI224G |
UCI224F |
UCI224F |
UCI274H |
|
AVR |
VITA 01 |
VITA 01 |
AS440 |
AS440 |
AS440 |
MX341 |
MX341 |
MX341 |
MX341 |
|
Insulation |
Class H |
Class H |
Class H |
Class H |
Class H |
Class H |
Class H |
Class H |
Class H |
HNI 250-1000 Technical Data
|
Spec |
HNI 250 |
HNI 300 |
HNI 350 |
HNI 450 |
HNI 500 |
HNI 650 |
HNI 800 |
HNI 1000 |
|---|---|---|---|---|---|---|---|---|
|
Standby Power (kW) |
250 |
300 |
350 |
448 |
500 |
650 |
800 |
1000 |
|
Standby Power (kVA) |
312 |
375 |
437.5 |
560 |
625 |
812.5 |
1000 |
1250 |
|
Amps @ 208V |
867 |
1040 |
1214 |
1555 |
1734 |
2255 |
2775 |
N/A |
|
Amps @ 480V |
375 |
451 |
526 |
673 |
751 |
977 |
1203 |
1503 |
|
Amps @ 600V |
300 |
360 |
421 |
541 |
601 |
782 |
962 |
1202 |
|
Sound @ 23' / 100% Load |
81 |
81 |
TBD |
79 |
79 |
84 |
84 |
79 |
|
Ambient Capability °F/°C |
114/46 |
114/46 |
114/46 |
114/46 |
114/46 |
122/50 |
118/48 |
122/50 |
|
NG Fuel Consumption ft³/h |
3,979 |
3,979 |
4,144 |
4,320 |
4,760 |
7,309 |
9,254 |
11,568 |
|
Engine Manufacturer |
PSI |
PSI |
PSI |
PSI |
PSI |
PSI |
PSI |
PSI |
|
Engine Model |
13L HO |
13L HO |
14.6L HO |
21.9L |
21.9L HO |
32L |
40L |
53L |
|
EPA Certified |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Engine HP |
469 |
469 |
536 |
684 |
764 |
966 |
1234 |
1589 |
|
Stamford Alternator |
S4L1D-C |
S4L1D-D |
S4L1D-E |
S4L1D-G |
S5L1D-D |
S5L1D-F |
S6L1D-C4 |
S6L1D-E4 |
|
AVR |
MX341 |
MX341 |
MX341 |
MX341 |
MX341 |
MX341 |
MX341 |
MX341 |
|
Insulation |
Class H |
Class H |
Class H |
Class H |
Class H |
Class H |
Class H |
Class H |
Dimensions and weights vary by model and selected configuration. Refer to the HIPOWER HNI brochure for detailed dimensional data. Specifications and designs are subject to change.
MEG Services Support for HIPOWER HNI Generators
MEG Services provides ongoing support for HIPOWER HNI standby generator systems, including maintenance, testing, repairs, transfer switch service, and emergency response.
Preventative Maintenance
Scheduled maintenance agreements, inspections, oil and filter service, coolant checks, battery testing, and other routine service to help keep standby systems ready.
Testing & Technical Support
Load bank testing, technical analysis, infrared inspection, megger testing, tank inspection, and generator troubleshooting.
Repairs & Emergency Service
24/7 emergency response, cooling system service, controller upgrades, transfer switch service, and generator repair support.
Request HIPOWER HNI Generator Sales or Service Support
Need help with sizing, pricing, configuration, service, or support for a HIPOWER HNI standby generator? Contact MEG Services for assistance.
HIPOWER HNI Resources
Review the full HIPOWER HNI product brochure or return to the main HIPOWER standby generator page.